LAPP KABEL H07RN-F - Enhanced Version, Halogen-free, Long-run submersion, UV and Oil Resistant Rubber Control Cable
Call or Email for Pricing
Share:
Halogen-free; Long-run submersion; Bending/Loop Torsion (WTG): -40°C to +90°C; UV/Ozone resistant
- Arrangements made of single-core, rubbersheathed cables H07RN-F can be used for short circuit-proof and short-to-groundproof installations in accordance with IEC 60364-5-52/ HD 60364-5-52/ VDE 0100 Part 520
- More water-resistant than H07RN-F and H07RN8-F
- Conductor temperature range more suitable for outdoor installation and wider than H07RN-F, H07ZZ-F, H07BN4-F and NSSHÖU
Application
- Medium, mechanical stress and industrial and agricultural use as well as for handheld and power supply devices (H07RN-F according to EN 50565-2)
- Drip loop torsion between the nacelle and the tower of wind turbine generators/windmills
- Outdoors acc. EN 50565-2
- For buildings or industrial plants with a high density of people or valuable assets
Product Features
- Oil resistant according to EN 60811-404; Good resistance to abrasion, atmospheric agents, grease and mineral oils
- UV-, Ozone- (acc. EN 60811), Cold- (-40 °C flexible at the conductor) and Heat resistant (+90 °C at the conductor)
- Drip loop torsion resistant (wind turbine) ==>TW-0, TW-1 and TW-2: -40 °C to +90 °C / 2,000 cycles (5,000 cycles from +5 °C)/torsion angle of +/-150 ° per metre at one revolution per minute
- Long-time water submersion (AD8) down to 100 m without interruption (no drinking water, minimum water temperature of +5 °C, standing water only, no areas with boat/ ship/ submarine traffi c)
- Halogen-free acc. EN 50267-2 (sub-parts -1 and -2), fl ame-retardant according to IEC 60332-1-2 and low smoke density (LS) acc. EN 61034-2
Approvals
- <HAR> H07RN-F cable type approval according to EN 50525-2-21
Cable Make-up
- Strands of bare copper wires
- Core insulation: special rubber
- Outer sheath: special rubber compound